WattNode® Plus for LonWorks® - Options
| AC Power Measurement, for LonWorks® Networks, Reactive Power, VARs, Power Factor, Individual Phase Measurements |
|
Click the downloads tab for options manuals, external interface files XIF, etc.
Data Logging
If you need data logging, see WattNode Logger for LonWorks
Option CT
- Option CT=xxx - Pre-assign xxx as the nciCtAmps value.
- This can be field configured or overridden using the nciCtAmps network variable.
Option B
If you need a WattNode meter that behaves like the old WNB series models (model numbers WNB-xx-xxx-FT10), then order a
- WNC-xx-xxx-FT10 Opt B
The Option B WattNode models are very similar to the original WNB series WattNode Plus models, but with a few changes:
- New program ID: 8:00022:1500:0A04:05. Because there are some hardware changes, LonMaker® requires a new program ID.
- Energy and time of day are stored to non-volatile memory every 5 seconds. The old version stored these every 20 seconds.
- The energy log has been removed (see our WattNode Logger for LonWorks if you need logging). The nviLogRequest and nvoLogData variables still exist, but do nothing.
- The network variable list is identical to the original WNB series WattNode Plus
- Firmware Version 3.03
- Downloads
Option BI
If you need a WattNode meter that behaves like the old WNB series models the integer output Option (models numbers WNB-xx-xxx-FT10), then order a
- WNC-xx-xxx-FT10 Opt BI
The Option BI WattNode models are very similar to the original WNB series WattNode Plus models with integer outputs, but with a few changes:
- New program ID: 9:00022:1500:0A:04:0B. Because there are some hardware changes, LonMaker requires a new program ID.
- New XIF (external interface file)
- Energy and time of day are stored to non-volatile memory every 5 seconds. The old version stored these every 20 seconds.
- The energy log has been removed (see our WattNode Logger for LonWorks if you need logging). The nviLogRequest and nvoLogData variables still exist, but do nothing.
- The network variable list is identical to the original WNB series WattNode Plus with option I (Integer Output).
- Firmware version 3.13
- Downloads
Option PT
Option PT improves support for potential transformers (PTs), making it easier to use WattNode for LonWorks meters with medium voltage services. Specifically, Option PT adds a configuration property UCPTptRatio which configures the ratio of the external PT, allowing the meter to automatically scale the voltage, power, and energy readings.
- See WattNode LonWorks - Option PT for more information.