Actions

WNA Series WattNode® for LonWorks®

 :True RMS - AC Power Measurement
for LonWorks® Networks,

LonMarkCertified3 4.png

Wna3y208ft lg.jpg


This product line is no longer being sold, information is for legacy purposes.

The WNA Lonworks Output WattNode has been replaced with the WattNode Plus for LonWorks

Download a datasheet or a manual (PDF).

The WattNode® for LonWorks combines three true RMS instruments in one: watt meter, watt-hour meter and demand meter. Typical applications include energy monitoring, performance verification and sub-metering where accuracy at reasonable cost is essential.

Through the LonWorks network, the WattNode communicates power (watts), energy (kilowatt-hours), demand and alarm conditions.

Easy installation saves you time and money. The WattNode is small enough to fit entirely within a standard electrical panel and the screw terminals unplug for easy wiring. A twisted pair of wires is used to create the network. The WattNode complies with the LonMark Interoperability Guidelines, Version 3.0. These guidelines ensure a standard interface so that the WattNode may be rapidly configured to communicate with other nodes on the LonWorks network.

The complete WattNode family measures 1, 2 or 3 phases in delta (3 phase, 3 wire) or wye (3 phase, 4 wire) configurations. With voltage ratings from 120 to 600 VAC and current transformer (CT) ratings from 5 to 3000 amps, there is a WattNode combination to meet nearly all of your AC power measurement requirements.

Accuracy of the WattNode is 0.5% of reading over a wide range of power factor and harmonic content. The WattNode measures true RMS power even with leading or lagging power factor and chopped or distorted waveforms. This makes the WattNode ideal for monitoring motors and pumps controlled by variable speed drives.

To assure reliability and accuracy, each WattNode is tested and calibrated by a custom, automated production system. A key part of the production process is calibration with NIST traceable standards. To assure the initial calibration accuracy is maintained, the WattNode has been designed with fixed, precision resistors, not potentiometers, in its measurement circuit.

Our safe CTs, with integral burden resistors, produce a voltage proportional to the load current. At rated current the voltage is only 0.333 VAC. Split core CTs quickly install on existing wiring and solid core CTs can prevent tampering. Bus bar CTs are available in a variety of standard sizes, plus custom designs up to 10" x 10" (254mm x 254mm) and 4000A.

Features

Specifications

Measurement Configurations

Quantities Measured

Quantities Retained During Power Loss

LonMark Interoperability

Configuration Control

Electrical

Accuracy

Environmental

WattNode Dimensions

Mechanical Click on the image for a larger view.
  • Enclosure: High impact, UL rated, ABS plastic
  • Size: 143mm x 85mm x 32mm (5.63" x 3.34" x 1.25")
  • Connectors: Euroblock style detachable screw terminals (UL, CSA recognized)
    • Green: 22 - 12 AWG (1.0mm - 3.2mm), 600 V
    • Black: 26 - 16 AWG (0.6mm - 2.0mm), 300 V
Wna-dimensions.jpg

Models

Model VAC Phase
to Neutral
VAC Phase
to Phase
Phases Wires
WNA-1P-240-xxx 120 240 1 or 2 2 or 3
WNA-3Y-208-xxx 120 208-240 1, 2 or 3 4
WNA-3Y-400-xxx 230 400 1, 2 or 3 4
WNA-3Y-480-xxx 277 480 1, 2 or 3 4
WNA-3Y-600-xxx 347 600 1, 2 or 3 4
WNA-3D-240-xxx N/A 208-240 2 or 3 3
WNA-3D-480-xxx N/A 480 2 or 3 3

The transceiver suffix "-xxx" may be:

The delta models, WNA-3D-240-xxx and WNA-3D-480-xxx, are used only when neutral is not present.

Datasheet, Manual, XIF File, and Application Notes

 

Call Us Toll Free
888-928-8663
888-WATTNODE
Voice: 303-444-7422
FAX: 303-444-2903
sales@ccontrolsys.com

Continental Control Systems
3131 Indian Rd. Suite A
Boulder, CO 80301
USA