Actions

Metering System Accuracy

Overview

Continental Control Systems, LLC sells WattNode® electric energy meters, as well as current transformers (CTs). Each have accuracy specifications, but it is not always clear how to combine the accuracy specifications of the meter and the CTs to determine an overall system accuracy; this article tries to clarify that computation and provide some general system accuracy information for energy and power measurements made using our products.

This article does not address the accuracies of other reported values, such as voltage, current, power factor, or reactive power.

General Results

Notes

Combined Accuracies

Power Factor 1.00 0.866 Leading 0.50 Lagging
WattNode Accuracy (%) 0.5% 0.5% 0.5%
System Accuracy (%) 2.0% 3.0% 4.5%

Computations

The accuracy for real power and real energy is the same, since energy is just the integral of power over time. There are three primary sources of power errors:

For purposes of this computation, we are using rated accuracies, which should generally be the worst-case; the actual accuracy will generally be better than the rated accuracy.

Most current transformers have a phase angle error where the output waveform is shifted in time from the measured current. This is generally measured in degrees or minutes (of degrees). The phase shift is almost universally leading. This is counter-intuitive, because it would seem to imply that the CT is predicting the future and because CTs are inductive devices and inductors normally cause lagging phase shifts; nevertheless, a leading phase angle is correct. Standard WattNode meters are calibrated to compensate for CTs with a 1.0 degree leading phase. This is too much compensation for some solid-core low-phase angle CTs and is not enough compensation for many of the split-core CTs, which tend to have larger phase angle errors, but it provides a good compromise, reducing the average error due to the phase angle error.

M_g = 0.5% Meter gain / linearity error (percent of reading)
C_g CT gain / linearity error (percent of reading)
M_p = 1.0 Meter phase adjustment (degrees). Lagging = positive value
C_p CT phase angle error (degrees). Leading = negative value
P_f Load displacement power factor
T_p = C_p + M_p Phase angle error after applying WattNode meter correction (degrees)
L_p = \arccos(P_f) Phase angle between voltage and current in the load (degrees). Positive = lagging, which is more common for inductive loads like motors.
L_p' = L_p + T_p = \arccos(P_f) + C_p + M_p Measured V-I phase angle including CT phase angle error and meter adjustment
P_g = \frac{\cos(L_p')}{P_f} - 1 System error due to phase angle error
E = M_g + C_g + |P_g| Combine worst-case error

Sample Calculations

The following table uses the above equations to compute system accuracies for a few sample cases.

Mg Cg Mp Cp Pf Tp Lp Lp' Pg E
±0.5% ±1.0% 1.0° -2.0° 0.500 -1.0° 60.0° 59.0° 3.0% 4.5%
±0.5% ±1.0% 1.0° -1.0° 0.500 0.0° 60.0° 60.0° 0.0% 1.5%
±0.5% ±1.0% 1.0° -0.3° 0.500 0.7° 60.0° 60.7° -2.1% 3.6%
±0.5% ±1.0% 1.0° -2.0° 0.866 -1.0° 30.0° 29.0° 1.0% 2.5%
±0.5% ±1.0% 1.0° -1.0° 0.866 0.0° 30.0° 30.0° 0.0% 1.5%
±0.5% ±1.0% 1.0° -0.3° 0.866 0.7° 30.0° 30.7° -0.7% 2.2%

See Also


Keywords: meter, accuracy, system, overall, CT

 

Call Us Toll Free
888-928-8663
888-WATTNODE
Voice: 303-444-7422
FAX: 303-444-2903
sales@ccontrolsys.com

Continental Control Systems
3131 Indian Rd. Suite A
Boulder, CO 80301
USA