Measurement Categories (CAT III)

Measurement categories are defined by the CE and UL safety standard IEC 61010-1 and are used to indicate the ability of an instrument (like the WattNode® meter) to withstand voltage spikes without posing a shock hazard to the operator. An instrument should only be used at or below its rated measurement category and voltage. For example, most WattNode models are CAT III rated and can be used to monitor CAT I, CAT II, and CAT III circuits.

There are situations where the WattNode meter needs to monitor the main service entrance, which is classified as CAT IV. In this situation, the WattNode voltage inputs (green screw terminal block) must be connected in a breaker panel or panel board, downstream of a the main disconnect, breaker, or fuses. The line voltages at this location will be essentially identical to the voltages measured at the main disconnect, so the WattNode measurements will be accurate. There is another reason for connecting the WattNode voltage inputs downstream of the service entrance. The largest wire gauge that the voltage inputs terminal block will accept is #12 AWG and there is usually no safe way to connect this small of a wire to the large terminations (lugs) inside the main panel

 