Toroidal solid-core current transformers are more compact and accurate. You must disconnect the measured circuit to install solid core CTs, so they are better suited for new wiring or permanent installation.
- 0.333 Vac output at rated current
- Accuracy ±1% from 10% to 130% of rated current
- No exposed metal
- Phase angle <1 degrees
- UL & CE recognized for voltages up to 600 Vac
- 8 ft. twisted-pair wire, 600 Vac rated
- Qualified under the Buy American provision in the American Recovery and Reinvestment Act of 2009 (ARRA).
- Dimensional drawing
- CTT Solid-Core CT Datasheet (PDF)
|
|
- List prices for 1-3 piece quantities. Call for pricing on larger quantities.
| Model |
I.D. |
Rated Amps (yyy) |
Max. Amps |
Max. Wire Gauge |
MSRP |
| CTT-0300-yyy |
0.30" |
5, 15, 20, 30 |
40 |
10 AWG, 4* AWG |
$32 |
| CTT-0500-yyy |
0.50" |
15, 20, 30, 50, 60 |
80 |
2 AWG, 1/0* |
$33 |
| CTT-0750-yyy |
0.75" |
30, 50, 70, 100 |
130 |
3/0, 300* kcmil |
$35 |
| CTT-1000-yyy |
1.00" |
50, 70, 100, 150, 200 |
260 |
300 kcmil, 500* kcmil |
$37 |
| CTT-1250-yyy |
1.25" |
70, 100, 150, 200, 250, 300, 400 |
520 |
500 kcmil, 750* kcmil |
$43 |
- The CT suffix "-yyy" is the rated amps. The "I.D." is the inside diameter of the CT. The "Max. Amps" is the highest continuous current that the CT can handle.
- The "Max Wire Gauge" is the largest wire gauge that should fit through this size of CT.
- * These sizes may or may not fit, depending on the insulation thickness.
- Model List: CTT-0300-005, CTT-0300-015, CTT-0300-030, CTT-0500-015, CTT-0500-030, CTT-0500-050, CTT-0500-060, CTT-0500-080, CTT-0750-030, CTT-0750-050, CTT-0750-070, CTT-0750-100, CTT-1000-050, CTT-1000-070, CTT-1000-100, CTT-1000-150, CTT-1000-200, CTT-1250-070, CTT-1250-100, CTT-1250-150, CTT-1250-200, CTT-1250-250, CTT-1250-300, CTT-1250-400
Safety Note
Warning: Hazardous Voltages - Only qualified personnel or licensed electricians should install the WattNode meter and current transformers.