WattNode® Plus for LonWorks®

 

AC Power Measurement
for LonWorks® Networks,
True Power, kWh
Reactive Power,
VARs, Power Factor,
Individual Phase Measurements

LonMark Certified

WattNode Plus for LonWorks
  • Overview

  • Specifications

  • Models & Pricing

  • Downloads

  • Options

The WattNode Plus

The WattNode Plus is a kilowatt hour kWh energy meter that communicates on a LonWorks network and measures 1, 2, or 3 phases with voltages from 120 to 600 volts alternating current VAC and 5 to 6,000 amps in delta (phase to phase) and wye (phase to neutral) configurations. For built-in data logging, see the WattNode Logger for LonWorks.

Measurements

  • True RMS Power - Watts (Phase A, B, C, all phases)
  • Reactive Power - VARs (Phase A, B, C, all phases)
  • Power Factor (Phase A, B, C, all phases)
  • True RMS Energy - Watthours WH kWh (Phase A, B, C, all phases)
  • Reactive Energy - VAR-hours (All Phases)
  • AC Frequency
  • Computed RMS Voltage (Phase A, B, C)
  • Computed RMS Current (Phase A, B, C)
  • Demand
  • Peak Demand

Features

  • LonMark 3.4 Certified
  • Small form factor for easy installation inside most electrical panels, see a sample installation diagram.
  • Pluggable screw terminals for easy wiring
  • 0.5% nominal accuracy (see manual for details)
  • True RMS power even with leading or lagging power factor and chopped or distorted waveforms
  • Monitors variable speed drives, pumps, and motors
  • Safe CT's (current transformers), producing 0.333 VAC at rated current.
  • Split core CTs for quick installation
  • Solid core CTs are less expensive and prevent tampering
  • Custom and standard Bus Bar sized CTs
  • The WattNode communicates on a LonWorks TP/FT-10 free topology twisted-pair network using Echelon’s® LonTalk® network protocol.

WattNode is a registered trademark of Continental Control Systems LLC. LonMark, the LonMark logo and LonWorks are registered trademarks of Echelon Corporation

Electrical

  • Line powered
  • UL Listed
  • CE Mark
  • FCC Class A
  • Operating Voltage Range: 80% to 115% of nominal
  • Power Line Frequency: 50 or 60 Hz
  • CT Input: 0.333 VAC nominal, 0 - 0.5 VAC operating, 3 VAC maximum

Measurement Configurations

  • Three phase: 4 wire
  • Three phase: 3 wire

Communication

  • Transceiver: Echelon TP/FT-10
  • Bit Rate: 78 kbps
  • Maximum Nodes: 64 per subnet
  • Maximum Distance: 500–2700 meters
  • Maximum Stub Length:
    • Free Topology: Unlimited
    • Bus Topology: 3 meters

Accuracy

  • 0.5% nominal accuracy (see manual for details)

Environmental

  • Operating Temperature: -30° to 55°C
  • Humidity: Up to 90% RH (non-condensing

Case Dimensions

Mechanical  Click on the image for a larger view.

  • Enclosure:
    • High impact, ABS plastic
    • Flame Resistance Rating: 94V-0, IEC FV-0
    • Size: 143mm × 85mm × 38mm (5.63" × 3.34" × 1.5")
    • Weight: 295gm (10.4oz)
  • Connectors: Euroblock style pluggable terminal blocks
    • Green: 22 to 12 AWG (1.0mm - 3.2mm), 600 V
    • Black: 22 to 12 AWG (1.0mm - 3.2mm), 300 V

Pricing information for all models and products

Model VAC Phase
to Neutral
VAC Phase
to Phase
Electrical
Service Types
Neutral
Required
MSRP
WNC-3Y-208-FT10 120 208-240 1 Phase 2 Wire 120V with neutral
1 Phase 3 Wire 120V/240V
3 Phase 4 Wire 120V/208V
check $499
WNC-3Y-400-FT10 230 400 1 Phase 2 Wire 230V with neutral
3 Phase 4 Wire 230V/400V
check $499
WNC-3Y-480-FT10 277 480 3 Phase 4 Wire 277V/480V check $499
WNC-3Y-600-FT10 347 600 3 Phase 4 Wire 347V/600V check $549
WNC-3D-240-FT10 N/A 208-240 1 Phase 2 Wire 208V (No neutral)
1 Phase 2 Wire 240V (No neutral)
1 Phase 3 Wire 120V/240V
3 Phase 3 Wire 208V (No neutral)
3 Phase 4 Wire 120V/208V
  $499
WNC-3D-400-FT10 N/A 400 3 Phase 3 Wire 400V (No neutral)
3 Phase 4 Wire 230V/400V
  $549
WNC-3D-480-FT10 N/A 400-480 3 Phase 3 Wire 480V (No neutral)
3 Phase 4 Wire 277V/480V
  $549

List prices for 1 piece quantities. Call for pricing on larger quantities.

Prices effective May 1, 2009. Prices subject to change without notice.

Datasheet, Manual, XIF File, and Application Notes

Options

Option B - Emulates the WNB-xx-xxx-FT10 series of WattNode meters

Option BI - Emulates the WNB-xx-xxx-FT10 series of WattNode meters with option I (Integer Output).

Click the downloads tab for options manuals, external interface files XIF, etc.

Option B

If you need a WattNode that behaves like our old WNB series models (models numbers WNB-xx-xxx-FT10), then you should order a

WNC-xx-xxx-FT10 Option B. The Option B WattNode models are very similar to the original WNB series WattNode Plus models, but with a few changes:

  • New program ID: 8:00022:1500:0A04:05. Because there are some hardware changes, LonMaker requires a new program ID.
  • Energy and time of day are stored to non-volatile memory every 5 seconds. The old version stored these every 20 seconds.
  • The energy log has been removed (see our WattNode Logger for LonWorks if you need logging). The nviLogRequest and nvoLogData variables still exist, but do nothing.
  • The network variable list is identical to the original WNB series WattNode Plus
  • Firmware version 3.03
  • Firmware Update

Option BI

If you need a WattNode that behaves like our old WNB series models the integer output Option (models numbers WNB-xx-xxx-FT10), then you should order a WNC-xx-xxx-FT10 Option BI. The Option BI WattNode models are very similar to the original WNB series WattNode Plus models, but with a few changes:

  • New program ID: 9:00022:1500:0A:04:0B. Because there are some hardware changes, LonMaker requires a new program ID.
  • New XIF (external interface)
  • Energy and time of day are stored to non-volatile memory every 5 seconds. The old version stored these every 20 seconds.
  • The energy log has been removed (see our WattNode Logger for LonWorks if you need logging). The nviLogRequest and nvoLogData variables still exist, but do nothing.
  • The network variable list is identical to the original WNB series WattNode Plus with option I (Integer Output).
  • Firmware version 3.12
  • Firmware Update