Call Us Toll Free
888-928-8663
888-WATTNOD
Voice: (303)444-7422
FAX: (303)444-2903
Email:
sales@ccontrolsys.com
Continental
Control Systems
3131 Indian Rd.,
Suite A
Boulder, CO 80301
USA |
|
| |
|
|
WattNode® Logger for LonWorks®
AC Power Measurement and Logging
for LonWorks Networks,
True Power, kWh
Reactive Power,
VARs, Power Factor,
Individual Phase Measurements

|
 |
-
Overview
-
Specifications
-
Models & Pricing
-
Downloads
-
Options
The WattNode Logger
The WattNode Logger is a kilowatt hour (kWh) energy meter that communicates on a LonWorks network, and can log 24,000+ measurement records in non-volatile memory. The WattNode Logger measures 1, 2, or 3 phases with voltages from 120 to 600 volts alternating current VAC and 5 to 6,000 amps in delta (phase to phase) and wye (phase to neutral) configurations.
Measurements
- True RMS Power - Watts (Phase A, B, C, all phases)
- Reactive Power - VARs (Phase A, B, C, all phases)
- Power Factor (Phase A, B, C, all phases)
- True RMS Energy - Watthours WH kWh (Phase A, B, C, all phases)
- Reactive Energy - VAR-hours (All Phases)
- AC Frequency
- RMS Voltage (Phase A, B, C)
- Computed RMS Current (Phase A, B, C)
- Demand
- Peak Demand
Quantities Logged
- Date and Time
- Net Energy (A, B, C and Sum)
- Reactive Energy (Sum)
- Positive Energy (Sum)
- Real and Reactive Power (A, B, C and Sum)
- Voltage, Current and Power Factor (A, B, C)
- Demand
Features
- Logging intervals from 1 minute to 12 hours allows logging up to 250 days of data
- LonMark 3.4 Certified
- Small form factor for easy installation inside most electrical panels, see a sample installation diagram.
- Pluggable screw terminals for easy wiring
- 0.5% nominal accuracy (see manual for details)
- True RMS power even with leading or lagging power factor and chopped or distorted waveforms
- Monitors variable speed drives, pumps, and motors
- Safe CT's (current transformers), producing 0.333 VAC at rated current.
- Split core CTs for quick installation
- Solid core CTs are less expensive and prevent tampering
- Custom and standard Bus Bar sized CTs
- The WattNode communicates on a LonWorks TP/FT-10 free topology twisted-pair network using Echelon’s® LonTalk® network protocol.
WattNode is a registered trademark of Continental Control Systems LLC. LonMark and the LonMark Logo are managed, granted, and used by LonMark International under a license granted by Echelon Corporation
Electrical
- Line powered
- FCC Class B
- Operating Voltage Range: -80% to +115%
- Power Line Frequency: 50 or 60 Hz
- CT Input: 0.333 VAC nominal, 0 - 0.5 VAC operating, 3 VAC maximum
Measurement Configurations
- Three phase: 4 wire
- Three phase: 3 wire
Communication
- Transceiver: Echelon TP/FT-10
- Bit Rate: 78 kbps
- Maximum Nodes: 64 per subnet
- Maximum Distance: 500–2700 meters
- Maximum Stub Length:
- Free Topology: Unlimited
- Bus Topology: 3 meters
Accuracy
- 0.5% nominal (see manual for details)
- Time: ± 2 minutes a year (battery backed)
Environmental
- Operating Temperature: -30° to 55°C
- Humidity: Up to 90% RH (non-condensing)
Mechanical Click on the image for a larger view.
- Enclosure:
- High impact, ABS plastic
- Flame Resistance Rating: 94V-0, IEC FV-0
- Size: 143mm × 85mm × 38mm (5.63" × 3.34" × 1.5")
- Weight: 320gm (11.3oz)
- Connectors: Euroblock style pluggable terminal blocks
- Green: 22 to 12 AWG (1.0mm - 3.2mm), 600 V
- Black: 22 to 12 AWG (1.0mm - 3.2mm), 300 V
Pricing information for all models and products
| Model |
VAC Phase to Neutral |
VAC Phase to Phase |
Electrical Service Types |
Neutral Required |
MSRP |
| WNC-3Y-208-FT10-L |
120 |
208-240 |
1 Phase 2 Wire 120V with neutral
1 Phase 3 Wire 120V/240V
3 Phase 4 Wire 120V/208V |
 |
$595 |
| WNC-3Y-400-FT10-L |
230 |
400 |
1 Phase 2 Wire 230V with neutral
3 Phase 4 Wire 230V/400V |
 |
$628 |
| WNC-3Y-480-FT10-L |
277 |
480 |
3 Phase 4 Wire 277V/480V |
 |
$628 |
| WNC-3Y-600-FT10-L |
347 |
600 |
3 Phase 4 Wire 347V/600V |
 |
$680 |
| WNC-3D-240-FT10-L |
N/A |
208-240 |
1 Phase 2 Wire 208V (No neutral)
1 Phase 2 Wire 240V (No neutral)
1 Phase 3 Wire 120V/240V
3 Phase 3 Wire 208V (No neutral)
3 Phase 4 Wire 120V/208V |
|
$628 |
| WNC-3D-400-FT10-L |
N/A |
400 |
3 Phase 3 Wire 400V (No neutral)
3 Phase 4 Wire 230V/400V |
|
$680 |
| WNC-3D-480-FT10-L |
N/A |
400-480 |
3 Phase 3 Wire 480V (No neutral)
3 Phase 4 Wire 277V/480V |
|
$680 |
List prices for 1 piece quantities. Call for pricing on larger quantities.
Prices effective May 1, 2009. Prices subject to change without notice.
Datasheet, Manual, XIF File, and Application Notes
Options
There are currently no options available for the WattNode Logger.
Click the Downloads tab for manuals, external interface files XIF, etc.